MetaSystem TRIMOD 10 UPS

Download complete info
Home - Ups - Online Double Conversion - Modular - MetaSystem TRIMOD 10
Technical details
MetaSystem TRIMOD 10
Rated power (kVA)10
Active power (kW)8
Max power scalability VA (kVA)-
Max power scalability VA (kW)-
TechnologyOnline Double Conversion
UPS ArchitectureModular
Input
Input voltage (V)230 (single phase) / 400 (three phase + N)
Input voltage range (V)230 +15% -20% single-phase / 400 +15% -20% three-phase
Minimum operating voltage (V)-
Input current THD< 3%
Input power factor> 0,99
Input frequency (Hz)50 / 60 ± 2%
Output
Output voltage (V)230 ± 1% single-phase / 400 ± 1% three-phase
Output frequency (Hz)50 / 60 synchronized
Output current THD-
Wave formSinusoidal
Crest factor3,5 : 1
Efficiency-
Overload capacity200% for 5 s - 150% for 30 s
Batteries
Voltage (V)12
Capacity (AH)7,2 or 9
Runtime @ 50% load (min)-
Runtime @ 80% load (min)-
Runtime ExtendibilityYes
Other information
Weight (kg)110
Dimensions (mm)414 x 1345 x 628
Working temperature (0C)0 - 40
Relative humidity (non condensing)20% - 80%
Acoustic noise @ 1 m (dBA)42 - 46
StandardsEN 62040-1-1, EN 50091-2, EN 62040-3
Warranty (months)-